ZC-BPYJVP-3 * 2.5+3 * 0.5 flame retardant frequency conversion shielded cableScope of Application
This product is suitable for use as a power cable or electrical connection in frequency conversion control systems with an AC rated voltage of 0.6/1kV and below. The product has strong resistance to voltage surges and can withstand pulse voltages during frequency conversion. The cable has good shielding properties and effectively eliminates electromagnetic interference, reduces frequency conversion motor noise, and ensures stable system operation. Widely used in industries such as metallurgy, power, and petrochemicals.
Execution standard: Q/321084KLA080

ZC-BPYJVP-3 * 2.5+3 * 0.5 flame retardant frequency conversion shielded cableUsage characteristics
1. Rated AC voltage UO/U: 0.6/1kV
2. Long term working temperature of cable: PVC insulation at 70 ℃; Cross linked polyethylene insulation at 90 ℃; Silicone rubber insulation at 180 ℃; Fluoroplastic insulation at 200 ℃ and 260 ℃
3. Allowable bending radius of cable: 15 times the outer diameter of the cable
ZC-BPYJVP-3 * 2.5+3 * 0.5 flame retardant frequency conversion shielded cable
| Project | technical performance |
| rated voltage | 450/750V |
| Long term allowable operating temperature for conductors | Polyethylene is at 70 ℃; Cross linked polyethylene at 160 ℃ |
| Polyvinyl chloride insulated cables are: 70 ℃, 90 ℃, 105 ℃ | |
| Low smoke halogen-free flame-retardant polyolefin insulated cables are suitable for temperatures of 70 ℃ and 90 ℃ | |
| Recommended bending radius for cables | Cables with armor or wrapped shielding structures should not be less than 12 times the outer diameter of the cable; The remaining structural cables should not be less than 6 times the outer diameter of the cable. |
| Allowable laying temperature | Polyethylene sheathed cable -20 ℃ |
| PVC sheathed and low smoke halogen-free flame-retardant polyolefin cable: 0 ℃ | |
| Flame retardant properties | Can withstand the bundled combustion test specified in GB12666.5 (IEC332-3); The smoke concentration during the combustion of low smoke, low halogen, and low smoke halogen-free flame-retardant cables should comply with the provisions of GB12666.7 (IEC1034). |
Conductor DC resistance meter, insulation resistance meter
| cross-sectional area | Direct current resistance of conductor at 20 ℃ | |||||
| mm2 | No tin plating | tin-plating | ||||
| Class A | Class B | Soft structure | Class A | Class B | Soft structure | |
| 0.5 | 36 | 36 | 39 | 36.7 | 36.7 | 40.1 |
| 0.75 | 24.5 | 24.5 | 26 | 24.8 | 24.8 | 26.7 |
| 1 | 18.1 | 18.1 | 19.5 | 18.2 | 18.2 | 20 |
| 1.5 | 12.1 | 12.1 | 13.3 | 12.2 | 12.2 | 13.7 |
| 2.5 | 7.41 | 7.41 | 7.98 | 7.56 | 7.56 | 8.21 |
| 4 | 4.61 | 4.61 | - | 4.7 | 4.7 | - |
| 6 | 3.08 | 3.08 | - | 3.11 | 3.11 | - |
| 10 | - | 1.83 | - | - | - | - |
| area | Insulation resistance at 70 ℃ or 90 ℃ | |||||
| mm2 | Polyethylene insulation or cross-linked polyethylene insulation | Polyvinyl chloride or low smoke halogen-free flame-retardant polyolefin insulation | ||||
| Class A | Class B | Soft structure | Class A | Class B | Soft structure | |
| 0.5 | 0.14 | 0.13 | 0.13 | 0.014 | 0.014 | - |
| 0.75 | 0.12 | 0.11 | 0.11 | 0.012 | 0.014 | 0.011 |
| 1 | 0.11 | 0.1 | 0.1 | 0.011 | 0.013 | 0.01 |
| 1.5 | 0.11 | 0.1 | 0.1 | 0.011 | 0.01 | 0.01 |
| 2.5 | 0.11 | 0.9 | 0.9 | 0.01 | 0.009 | 0.009 |
| 4 | 0.085 | 0.07 | - | 0.0085 | 0.0077 | - |
| 6 | 0.07 | 0.065 | - | 0.007 | 0.0065 | - |