Welcome Customer !

Membership

Help

Baoding Yuxin Electric Technology Co., Ltd
Custom manufacturer

Main Products:

foodequippro>Products

Baoding Yuxin Electric Technology Co., Ltd

  • E-mail

    xuezhanyu@163.com

  • Phone

    13730155906、13730155903

  • Address

    1-1-5 Torch Industrial Park, No. 677 Jinxiu Street, Baoding City, Hebei Province

Contact Now

YX-YLM Voltage and Current Measurement Device

NegotiableUpdate on 01/01
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Overview of YX-YLM Voltage and Current Measurement Device 1 1.1 Overview This device is suitable for measuring voltage and current in 48V, 110V, and 220V DC systems. It can measure the ambient temperature on site, and the measured values of voltage, current, and temperature are transmitted through RS485 bus using Modbus communication protocol. The power supply voltage is 85-264VAC, 100-370VDC, or 36-75VDC optional

Product Details

YX-YLMVoltage and current measuring device

1Overview

1.1review

This device is suitable for48VThe110VThe220VThe measurement of DC system voltage and current can measure the ambient temperature on site, and the measured values of voltage, current, and temperature can be obtained throughRS485Bus transmission, usingmodbusCommunication protocol, power supply voltage85~264VAC100~370VDCor36~75VDCOptional.

The device is stable and reliable, and the power supply and voltage measurement circuit have anti reverse connection, overvoltage, and overcurrent protection; External opening and closing Hall sensor can measure positive and negative bidirectional currents;RS485support115200Baud rate, can be connected in parallel256A node with lightning protection and other protective measures. Customized services are supported for special application scenarios.

The device has a small volume, light weight, and uses a non-metallic shell to further reduce potential safety hazards during on-site use. It is an effective solution for high reliability and precision requirements of on-site voltage, current, and temperature detection in DC systems.

1.2technical indicators

device name

YX-YLMVoltage and current measuring device

power supply voltage

85~264VAC100~370VDCor36~75VDC

Voltage measurement range (customizable)

0~270V DC

Voltage measurement accuracy

0.1%

Current measurement range (customizable)

-100A ~ +100A DC

Accuracy of current measurement

1%

Temperature measurement range

-55~+125

Temperature measurement accuracy

±0.5

Operating Temperature

-10~80

RS485通信速率

4800~115200 bps

maximum supportRS485number of nodes

256

Power frequency withstand voltage (between different circuits)

2000Vrms/min

fast transient

Alevel

Overall dimensionsmm

198*91*46

fixation method

Tighten the screws on both sides

2Appearance and wiring instructions

2.1appearance

2.1wiring

The device has a single-sided outgoing line, and the corresponding names of the wiring terminals are shown on the labels in the following figure:

Power supplyAC/DC”: Connect power supply, AC/DC dual-use, optional85~264VAC100~370VDCor36~75VDC.

'Empty':thatThe terminal is an empty terminal with no electrical connection inside.

Voltage Test ": The input terminal of the DC voltage to be tested.

Current measurement:4Connect the terminal to the corresponding terminal on the external switchable DC Hall current sensor. The dimensions and terminal definitions of the switchable DC Hall current sensor are shown in the following figure“+12V”Connecting devices“12V”, sensors“-12V”Connecting devices“-12V”The sensor's“OUT”Connecting devices“IN”The sensor's“0V”Connecting devices“0V”. When the direction of current flow is consistent with the arrow on the sensor, the measurement result is positive, otherwise it is negative.

RS485”: Connect485Bus, among which“G”For485Signal ground rather than earth, determine whether to connect based on on-site usage.

Power indicator light: Always on when powered on.

Communication indicator light: flashes during communication.

Temperature measurement ": a temperature sensor used to measure the ambient temperature.