FS SYSTEM 10 is a high-speed, microprocessor based fire detection and process control system. It is designed specifically for liquid and powder coating applications, capable of quickly detecting flames and stopping the electrostatic coating process within milliseconds when flames are detected; And it can effectively interrupt the fire before the residue and wet paint film ignite.

Product Details

FS SYSTEM 10 is a high-speed, microprocessor based fire detection and process control system. It is designed specifically for liquid and powder coating applications, capable of quickly detecting flames and stopping the electrostatic coating process within milliseconds when flames are detected; And it can effectively interrupt the fire before the residue and wet paint film ignite.


Honeywell FS SYSTEM 10 Flame Detection/Process Control Product Introduction:

FS SYSTEM 10 is a high-speed, microprocessor based fire detection and process control system. It is designed specifically for liquid and powder coating applications, capable of quickly detecting flames and stopping the electrostatic coating process within milliseconds when flames are detected; And it can effectively interrupt the fire before the residue and wet paint film ignite.
FS SYSTEM 10 can provide a two-level response system: the 'warning' level is suitable for gun 'fireball' type fires; When the fire continues to spread, the 'fire alarm' level will sound within 4-5 seconds. The FS SYSTEM 10 flame detector has an electro-optic quantum infrared sensor matrix and can detect fires in the ground, resulting in false alarms. Therefore, its performance is significantly better than traditional detectors.
The detector should be installed inside an explosion-proof enclosure.
This controller is an independent system with indicator lights and requires installation inside a NEMA 12 (NEMA: National Electrical Manufacturers Association) enclosure.
The system integrates three 10A relays to timely stop paint flow, cut off static electricity, and transport. The 'history' and 'fault' files of the detector will be reported in real-time and then stored in the detector's non-volatile solid-state memory. You can download FirePic and SnapShot data from the RS 232 port of this controller using a personal computer.
This controller can operate with one or two detectors.


Honeywell FS SYSTEM 10 Flame Detection/Process Control Product Features:

Multi spectral infrared flame detector;
Compliant with NFPA 33 requirements (NFPA: National Fire Protection Association);
Unique two-level 'warning' and 'fire alarm' response;
No fault alarm caused by arc discharge and corona discharge;
Built in fully automatic 'internal light testing' self-test;
Not sensitive to local radiation sources such as paint heaters and generating false alarms;
Not affected by inhalation of smoke or paint solvent mist in the liquid spray booth;
Not affected by paint, powder, and residual oil on the lens;
Use RS-485 interface for digital communication;
FirePic ™: Realize the retrieval of historical fire archive data;
SnapShot ™: Dynamically display the situation detected by the detector through graphical representation.


Application areas of Honeywell FS SYSTEM 10 flame detection/process control products in the United States:

Liquid spray painting production line

Aerosol filling

Powder coating room

Transformer Room

Diesel engine and gas compressor station

boiler room





Technical parameters of Honeywell FS SYSTEM 10 flame detection/process control product:

Brand: HONEYWELL/Honeywell
model: FS SYSTEM 10TM
Working voltage: 120(V)
Alarm current: 24V(mA)
Detection angle: 90°
Static current: 200(uA)
Working temperature: -40~+185°F(-40~+85℃)(℃)
Detection distance: There are 9 meter and 14 meter sensitivities to choose from (m)
Transmission frequency: 50(MHZ)
Scope of application: 4.5
Type: Infrared alarm detector
Installation method: Wall Mount
Launch distance: 9/14(m)
Action distance: 20(mm)
Communication method: wired
Weight: 1800(g)
Alarm method: RS-485
Technical specifications - Wall mounted controller
Protective shell EMA 12 wall mounted stainless steel cabinet
Display and indication 24 character backlit LCD
LED status indicator light
Built-in Speakers
Input power 18~28VDC, Rated 24VDC
120V DC with optional kit
power consumption Normal situation: 200mA at 24V DC
Alarm situation: 180mA at 24V DC
Relay Warning: Single pole double throw, passive contact;
Warning: Single pole double throw, passive contact;
Fire alarm: single pole double throw, passive contact;
Fault: Single pole double throw, active contact;
Process control: (3) Single pole double throw, active contacts
Relay contact rating:
Process control: 10A @ 24VDC
All other relays: 1A @ 24VDC
Under normal operating conditions, both process control and fault relays have active outputs, while all other relays have passive outputs.
operation temperature +32 to+122 degrees Fahrenheit (0 to+50 degrees Celsius)
Electrical connection RS-485 interface, using shielded four core cable FireBus circuit
FirePicTM 6 items in total, 8 seconds per week
Event history Two detectors, 200 pieces
Number of detectors 1-2 detectors per controller
Technical Specifications - Detector
sensitivity 4.5-meter standard sensitivity
There are 9 meter and 14 meter sensitivities to choose from. Please declare when placing an order
response time Warning 0.3 seconds
Warning for 0.5 seconds
Alarm for 4 seconds
field of view Within 90 ° range (horizontal and vertical)
Weight 3.8 pounds (1.7 kilograms)
temperature range -40~+185°F(-40~+85℃)
Shell cast aluminium
The protection level is NEMA 4
Electrical grade Class I, Div. 1 and 2, Groups B, C, and D
spectral sensitivity Near infrared: 700 to 1100nm
Broadband infrared: 700 to 3500nm
Visible light: 400 to 700nm