24/7 explosion-proof flame retardant breathing valve

NegotiableUpdate on 10/22
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Introduction to ZFQ-2 all-weather explosion-proof flame retardant breathing valve. This product integrates flame arrester and breathing valve, and its novel structure is the first of its kind in China

Product Details

24/7 explosion-proof flame retardant breathing valveintroduction
ZFQ-2The all-weather explosion-proof flame arrester breathing valve integrates a flame arrester and a breathing valve, and its novel structure is the first of its kind in China. It is a new type of safety equipment essential for petrochemical storage tanks, with the greatest advantages of good flame retardant breathing performance, light weight, and easy maintenance. This product is suitable for storage with an internal point lower than 28 Class A oil products with a flash point below ℃ 60 Class B oil products with a temperature of ℃, such as gasoline, benzene, toluene, kerosene, light diesel, engine oil, crude oil, and chemical products with the same properties, are used in storage tanks -35 -60
Normal operation in a temperature environment of ℃.
Operating pressure: Positive pressure: 353Pa (36mmH2O) 980.7Pa (100mmH2O) Negative pressure: 294.2Pa (30mmH2O)

24/7 explosion-proof flame retardant breathing valveworking principle
ZFQ-2The all-weather explosion-proof flame retardant breathing valve is installed on the top of the storage tank, which not only has flame retardant function but also solves the problem of positive and negative pressure gas inside the tank, so that the liquid in and out of the tank is not obstructed. When the external liquid is input into the tank, a large amount of gas is exhaled to the outside (called positive pressure). When the liquid inside the tank is exported, it must be sucked into the tank from the outside air (called negative pressure). If the breathing valve automatically closes when the work stops, it will not leak the liquid and gas inside the tank, which ensures the quality of the liquid inside the tank.

24/7 explosion-proof flame retardant breathing valvestructural diagram

Technical Specifications

A-grade positive pressure
355Pa (36mm water column)
negative pressure
295Pa (30mm water column)
B-level positive pressure
980Pa (100mm water column)
negative pressure
295Pa (30mm water column)
C-level positive pressure
1765Pa (180mm water column)
negative pressure
295Pa (30mm water column)

Component materials

Valve body material
Carbon steel WCB, stainless steel 304, 316, aluminum alloy
Positive pressure valve disc material
Stainless steel 304, 316, aluminum alloy
Negative pressure valve disc material
Stainless steel 304, 316, PTFE PTFE
Environmental temperature ℃
-30~60
Operating pressure Pa
-295~98000  -30mmH2O~+10000mmH2O
National standard flange connection external dimensions: GB, JB

Specifications
Installation size (mm)
D1
D
D3
H
M-h
DN50
110
140
160
255
4×12
DN100
170
205
235
480
4×16
DN150
225
260
295
547
8×16
DN200
280
315
355
658
8×16
DN250
335
370
420
705
12×16
American standard flange connection dimensions: ANSI, API, ASME available for JIS standards

Specifications
Installation size (mm)
D1
D
D3
H
M-h
2'
120.5
152
160
255
4×19
4'
190.5
229
265
290
8×19
6'
241.5
254
305
330
8×22
8'
298.5
343
355
350
8×22
10'
362
406
420
400
12×25

24/7 explosion-proof flame retardant breathing valvemaintenance and repair
To ensure the normal use of the all-weather explosion-proof flame retardant breathing valve
1. The corrugated fire-resistant layer should be regularly removed and cleaned within 3-6 months to ensure that each hole on the fire-resistant layer is unobstructed, prevent blockage, and ensure safe and normal use.
2. Regularly check whether the positive and negative valve discs of the ventilation are flexible, and whether the contact seal between the guide rod and the valve disc is damaged. If there is any damage, it should be replaced immediately.
3. During inspection, maintenance, and reinstallation, it should be ensured that the joint surfaces inside the valve are tightly matched and the valve disc can be lifted and lowered flexibly.
When using a new valve, the shock absorbers between the valve discs should be removed before installation, otherwise the breathing valve will malfunction.